# The Acetylene Safety (England and Wales and Scotland) Regulations 2014, Paragraph 9: Interpretation


In this Schedule—
“acetylene burner” means any equipment, including devices and valves, designed for use with ignited acetylene gas;
“acetylene-consuming equipment” means any equipment designed to convert acetylene gas into another chemical form;
“flame arrestor” means a device designed and constructed to arrest the progression of any flame resulting from the decomposition or uncontrolled combustion of acetylene gas;
“system of connected acetylene equipment” means any connected equipment, whether permanently or temporarily connected, which is intended for use with compressed acetylene gas, or which is used with compressed acetylene gas, including acetylene equipment, a cylinder, an acetylene manifold and other accessories; and
“quick-acting shut-off device” means a safety device effective against the continued release of—
(a) acetylene gas; and
(b) products of decomposition caused by—
(i) the decomposition of acetylene gas; or
(ii) any uncontrolled combustion of acetylene gas.
Table
Pipework maximum internal diameter
(mm)
Maximum pressure of contained compressed acetylene gas (bar(g))
23
1.5
25
1.3
35
1.0
42
0.8

---