Schedule 2 THE EFFICIENCY REQUIREMENTS

Original text. Later amendments are not shown.

Boilers must comply with the useful efficiency requirements set out in the Table below —

(a)

at rated output, that is, operating at rated output Pn expressed in kW, at an average boiler-water temperature of 70°C, and

(b)

at part load, that is, operating at 30% part load, at an average boiler-water temperature which varies according to the type of the boiler.

Table

Type of boilerRange of power outputEfficiency at rated outputEfficiency at part load
kWAverage boiler-water temperature expressed in °CEfficiency requirement expressed in %Average boiler-water temperature expressed in °CEfficiency requirement expressed in %
*

Including condensing boilers using liquid fuels.

**

Temperature of boiler water supply.

Standard boilers4 to 40070≥84 + 2 log Pn≥50≥80 + 3 log Pn
Low temperature boilersf14 to 40070≥87.5 + 1.5 log Pn40≥87.5 + 1.5 log Pn
Gas condensing boilers4 to 40070≥91 + 1 log Pn30f2≥97.1 + 1 log Pn