# The Boiler (Efficiency) Regulations 1993, Part III: Efficiency requirements to be met both at nominal output and at part load 0.3 Pn


Label
Efficiency requirement at nominal output Pn and at an average boiler-water temperature of 70°C %
Efficiency requirement at part load of 0.3 Pn and at an average boiler-water temperature of ≥50°C %
★
≥84 + 2 log Pn
≥80 + 3 log Pn
★★
≥87 + 2 log Pn
≥83 + 3 log Pn
★★★
≥90 + 2 log Pn
≥86 + 3 log Pn
★★★★
≥93 + 2 log Pn
≥89 + 3 log Pn

---