  "url": "https://openlegislation.uk/building-regulations-amendment-no-2-regulations-1999/regulation-3",
  "json_url": "https://openlegislation.uk/building-regulations-amendment-no-2-regulations-1999/regulation-3.json",
  "legislation": "uksi/1999/3410",
  "legislation_title": "The Building Regulations (Amendment) (No. 2) Regulations 1999",
  "legislation_url": "https://openlegislation.uk/building-regulations-amendment-no-2-regulations-1999",
  "path": "regulation/3",
  "kind": "regulation",
  "number": "3",
  "heading": "Amendment of the Building Regulations 1991",
  "text": "For Part B (Fire Safety) there shall be substituted the following part–\n“PART B\nFIRE SAFETY\nMeans of warning and escape\nB1 The building shall be designed and constructed so that there are appropriate provisions for the early warning of fire, and appropriate means of escape in case of fire from the building to a place of safety outside the building capable of being safely and effectively used at all material times.\nRequirement B1 does not apply to any prison provided under section 33 of the Prisons Act 1952 (power to provide prisons etc.).\nInternal fire spread (linings)\nB2 —\n(1) To inhibit the spread of fire within the building the internal linings shall–\n(a) adequately resist the spread of flame over their surfaces; and\n(b) have, if ignited, a rate of heat release which is reasonable in the circumstances.\n(2) In this paragraph “internal linings” mean the materials lining any partition, wall, ceiling or other internal structure.\nInternal fire spread (structure)\nB3 —\n(1) The building shall be designed and constructed so that, in the event of fire, its stability will be maintained for a reasonable period.\n(2) A wall common to two or more buildings shall be designed and constructed so that it adequately resists the spread of fire between those buildings. For the purposes of this sub-paragraph a house in a terrace and a semi-detached house are each to be treated as a separate building.\n(3) To inhibit the spread of fire within the building, it shall be sub-divided with fire-resisting construction to an extent appropriate to the size and intended use of the building.\nRequirement B3(3) does not apply to material alterations to any prison provided under section 33 of the Prisons Act 1952.\n(4) The building shall be designed and constructed so that the unseen spread of fire and smoke within concealed spaces in its structure and fabric is inhibited.\nExternal fire spread\nB4 —\n(1) The external walls of the building shall adequately resist the spread of fire over the walls and from one building to another, having regard to the height, use and position of the building.\n(2) The roof of the building shall adequately resist the spread of fire over the roof and from one building to another, having regard to the use and position of the building.\nAccess and facilities for the fire service\nB5 —\n(1) The building shall be designed and constructed so as to provide reasonable facilities to assist fire fighters in the protection of life.\n(2) Reasonable provision shall be made within the site of the building to enable fire appliances to gain access to the building.\n”",
  "extent": null,
  "status": null,
  "version": "current",
  "annotations": [
    {
      "type": "footnote",
      "label": "f1",
      "text": "1952 c. 52."
    }
  ],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/uksi/1999/3410/regulation/3",
    "retrieved_at": "2026-10-29T09:29:32.055702+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}