# The Building Regulations (Northern Ireland) 2012, Regulation 69: Application and interpretation


(1) Any provision in regulations 70 to 74 and 77 which applies to a combustion appliance, shall also apply where solid fuel is intended to burn directly on a hearth without the installation of any appliance.
(2) Regulation 72 shall not apply to a combustion appliance designed solely for cooking purposes.
(3) Regulation 75 shall only apply to a liquid fuel storage tank and connecting pipework located outside the building, which serves a fixed combustion appliance within the building and which is—
(a) a fixed oil storage tank with a capacity greater than 90 litres; or
(b) a fixed liquefied petroleum gas storage tank with a capacity greater than 150 litres.
(4) Regulation 76 shall only apply to an above ground fixed oil storage tank, which serves a dwelling and to which any one of the following applies—
(a) it has a capacity of more than 2500 litres but less than 3500 litres;
(b) it is located within 10 m of inland freshwaters or coastal waters;
(c) it is located within 50 m of a source of potable water, such as a well, bore-hole or spring;
(d) it is located where spilled oil from the installation could reach the waters in (b) or (c) by running across hard ground;
(e) it is located where spillage could run into an open drain or loose fitting manhole cover; or
(f) it is located where the tank vent pipe outlets cannot be seen from the intended filling point.
(5) In this Part—
“Combustion appliance” means a fixed appliance (including a cooker) which—
(a)is designed to burn solid fuel, gas or oil; or
(b)is an incinerator.

---
Source: https://www.legislation.gov.uk/nisr/2012/192/regulation/69 (the official version)
Page: https://openlegislation.uk/building-regulations-northern-ireland-2012/regulation-69
Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives.