# The Clean Air (Emission of Grit and Dust from Furnaces) Regulations 1971, Paragraph 3: Quantities which may be emitted


(1) Subject to the provisions of paragraph 4 below, the quantities of grit and dust, in pounds per hour, which may be emitted by the chimney of a schedule 1 furnace the heat output of which is within the highest and lowest values specified in column (1) of the following table shall not exceed—
(a) if the furnace burns solid matter, the quantities prescribed in column (2) against the value representing the output of that furnace or
(b) if the furnace burns liquid matter, the quantities prescribed in column (3) against that value.
Maximum Continuous Rating in pounds of steam per hour (from and at 100°C. (212°F.)) or in thousands of British thermal units per hour
Maximum permitted quantities of grit and dust in pounds per hour
Furnaces burning solid matter
Furnaces burning liquid matter
(1)
(2)
(3)
825
1.10
0.25
1,000
1.33
0.28
2,000
2.67
0.56
3,000
4.00
0.84
4,000
5.33
1.12
5,000
6.67
1.4
7,500
8.50
2.1
10,000
10.00
2.8
15,000
13.33
4.2
20,000
16.67
5.6
25,000
20.0
7.0
30,000
23.4
8.4
40,000
30
11.2
50,000
37
12.5
100,000
66
18
150,000
94
24
200,000
122
29
250,000
149
36
300,000
172
41
350,000
195
45
400,000
217
50
450,000
239
54.5
475,000
250
57

---