Paragraph 3 Quantities which may be emitted
Subject to the provisions of paragraph 4 below, the quantities of grit and dust, in pounds per hour, which may be emitted by the chimney of a schedule 2 furnace the heat input of which is within the highest and lowest values specified in column (1) of the following table shall not exceed—
(a)
if the furnace burns solid matter, the quantities prescribed in column (2) against the value representing the heat input of that furnace or
(b)
if the furnace burns liquid matter, the quantities prescribed in column (3) against that value.
| Heat input in millions of British thermal units per hour | Maximum permitted quantities of grit and dust in pounds per hour | |
|---|---|---|
| Furnaces burning solid matter | Furnaces burning liquid matter | |
| (1) | (2) | (3) |
| 1.25 | 1.1 | 0.28 |
| 2.5 | 2.1 | 0.55 |
| 5.0 | 4.3 | 1.1 |
| 7.5 | 6.8 | 1.7 |
| 10 | 7.6 | 2.2 |
| 15 | 9.7 | 3.3 |
| 20 | 11.9 | 4.4 |
| 25 | 14.1 | 5.5 |
| 30 | 16.3 | 6.6 |
| 35 | 18.4 | 7.7 |
| 40 | 20.6 | 8.8 |
| 45 | 22.8 | 9.8 |
| 50 | 25 | 10.9 |
| 100 | 45 | 16 |
| 200 | 90 | 26 |
| 300 | 132 | 35 |
| 400 | 175 | 44 |
| 500 | 218 | 54 |
| 575 | 250 | 57 |