Paragraph 2
The fuel oil storage area shall be surrounded by a bund capable of retaining within the area–
in a case where all the fuel oil within the storage area is contained in one fuel storage tank, a volume of fuel oil not less than 110 per cent of the capacity of the tank;
in a case where all the fuel oil within the storage area is contained in more than one fuel storage tank, a volume of fuel oil not less than whichever is the greater of–
110 per cent of the capacity of the largest tank within the storage area; and
25 per cent of the total volume of such oil which could be stored in tanks within the area;
in any other case, a volume of fuel oil not less than whichever is the greater of–
110 per cent of the capacity of the largest container within the storage area; and
25 per cent of the total volume of such oil at any time stored within the area.