# The Electricity and Gas (Internal Markets and Network Codes) (Amendment etc.) (EU Exit) Regulations 2020, Paragraph 19


(1) Article 25 (voltage stability requirements applicable to AC-connected offshore power park modules) is amended as follows.
(2) Omit paragraph 2.
(3) In paragraph 3—
(a) omit the words from “Notwithstanding the provisions” to “Continental Europe synchronous area”;
(b) for Table 10 substitute—
“
Table 10
Synchronous area
Voltage range
Time period for operation
Great Britain
0.90 pu – 1.10 pu where the voltage base for pu values is below 300kV
Unlimited
0.90 pu – 1.05 pu where the voltage base for pu values is from 300kV to 400kV
Unlimited
1.05 pu – 1.10 pu where the voltage base for pu values is from 300kV to 400kv
15 minutes
”
(4) In paragraph 5, for Table 11 substitute—
“
Table 11
Parameters for Figure 8
Synchronous area
Maximum range of Q/Pmax
Maximum range of steady-state voltage level in PU
Great Britain
0, at the offshore connection point for configuration 1 (as described in Article 23(3)(a)).
0.225
0.33, at the offshore connection point for configuration 2 (as described in Article 23(3)(b)).
0.225
”

---