# The Environmental Protection (Disposal of Polychlorinated Biphenyls and other Dangerous Substances) (Amendment) Regulations (Northern Ireland) 2025, Regulation 4: Amendment of regulation 4


In regulation 4—
(1) in paragraph (1), for “, (3)”, substitute “to (3C)”;
(2) for paragraph (3), substitute—
“(3) Paragraph (3A) applies to a transformer in respect of which it is reasonable to assume that it contains—
(a) 0.005% by weight, or less, of PCBs within the fluids containing PCBs; or
(b) a total volume of 0.05dm3, or less, of fluids containing PCBs.
(3A) A transformer to which this paragraph applies—
(a) may be held until the end of its useful life; and
(b) must then be decontaminated in accordance with paragraph (4)(b) to (d), or disposed of, as soon as possible.
(3B) Paragraph (3C) applies to a transformer in respect of which it is reasonable to assume that it contains—
(a) more than 0.005% but no more than 0.05% by weight of PCBs within the fluids containing PCBs; and
(b) a total volume of more than 0.05dm3 of PCBs fluids containing PCBs.
(3C) A transformer to which this paragraph applies—
(a) may be held until the end of 31st December 2025; and
(b) must then be decontaminated in accordance with paragraph (4)(b) to (d), or disposed of, as soon as possible.”
(3) in paragraph (4)(a), for “less than 0.05% by weight and, if possible, to no more than 0.005% by weight” substitute “0.005% by weight, or less, or to reduce the total volume of fluids containing PCBs to 0.05dm3, or less”.
(4) In regulation 4(8)—
(i) in sub-paragraph (a), for “, (3)” substitute “to (3C)”;
(ii) in sub-paragraphs (b) and (c), for “not contaminated”, in both places it occurs, substitute “relevant”;
(iii) after paragraph (8) insert—
“(9) In paragraph (8), “relevant equipment” means any equipment (including any capacitor or receptacle containing residual stocks) which—
(a) contains PCBs; or
(b) having contained PCBs, has not been decontaminated, other than one which contains a total volume of PCBs exceeding 0.05dm3.
(10) For the purposes of paragraph (9)—
(a) the PCB volume of a power capacitor shall be measured by reference to all of the separate elements of a combined set; and
(b) anything of a type which may contain PCBs shall be treated as containing PCBs unless it is reasonable to assume the contrary.”

---
Source: https://www.legislation.gov.uk/nidsr/2025/9780338024916/regulation/4 (the official version)
Page: https://openlegislation.uk/draft-environmental-protection-disposal-of-polychlorinated-biphenyls-and-other-dangerous-substances-amendment-regulations-northern-ireland-2025/regulation-4
Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives.