(1)

All occupied areas in a school building shall have controllable ventilation at a minimum rate of 3 litres of fresh air per second for each of the maximum number of persons the area will accommodate.

(2)

All teaching accommodation, medical examination or treatment rooms, sick rooms, isolation rooms, sleeping and living accommodation shall also be capable of being ventilated at a minimum rate of 8 litres of fresh air per second for each of the usual number of people in those areas when such areas are occupied.

(3)

All washrooms shall also be capable of being ventilated at a rate of at least six air changes an hour.

(4)

Adequate measures shall be taken to prevent condensation in, and remove noxious fumes from, every kitchen and other room in which there may be steam or fumes.