OpenLegislation

Regulation 20 Heating

Original text. Later amendments are not shown.

(1)

Each room or other space in a school building shall have such a system of heating, if any, as is appropriate to its normal use.

(2)

Any such heating system shall be capable of maintaining in the areas set out in columm (1) of the Table below the air temperature set out opposite thereto in column (2) of that Table, at a height of 0.5 m above floor level when the external air temperature is –1°C.

TABLE

(1)(2)
AreasTemperature
Areas where there is a lower than normal level of physical activity because of sickness or physical disability including sick rooms and isolation rooms but not other sleeping accommodation21°C
Areas where there is the normal level of physical activity associated with teaching, private study or examinations18°C
Areas where there is a higher than normal level of physical activity (for example arising out of physical education) and washrooms, sleeping accommodation and circulation spaces.15°C
(3)

Each room or other space which has a heating system shall, if the temperature during any period during which it is occupied would otherwise be below that appropriate to its normal use, be heated to a temperature which is so appropriate.

(4)

In a special school, nursery school or teaching accommodation used by a nursery class in a school the surface temperature of any radiator, including exposed pipework, which is in a position where it may be touched by a pupil shall not exceed 43°C.