# The Electrical Luminous Tube Signs (Scotland) Regulations 1990, Regulation 3: Fireman’s emergency switches


Apparatus shall be provided with a fireman’s emergency switch which–
(a) either
(i) complies with regulation 4; or
(ii) although not complying with regulation 4, is so installed as to satisfy the fire authority that it would be readily recognised by, and accessible to, firefighters; and
(b) is provided with a lock or catch to prevent the switch being inadvertently returned to the “on” position.

---