  "heading": "MINIMUM HEIGHT ABOVE GROUND OF OVERHEAD LINES",
  "text": "Column 1\nColumn 2\nColumn 3\nNominal Voltages\nOver Roads\nOther Locations\nNot exceeding 33,000 volts\n5.8 metres\n5.2 metres\nExceeding 33,000 volts but not exceeding 66,000 volts\n6 metres\n6 metres\nExceeding 66,000 volts but not exceeding 132,000 volts\n6.7 metres\n6.7 metres\nExceeding 132,000 volts but not exceeding 275,000 volts\n7 metres\n7 metres\nExceeding 275,000 volts but not exceeding 400,000 volts\n7.3 metres\n7.3 metres",
  "extent": null,
  "status": null,
  "version": "current",
  "annotations": [],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/uksi/2002/2665/schedule/2",
    "retrieved_at": "2026-10-29T06:43:15.022339+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}