Regulation 8 Earthing of metalwork

Changes not yet applied. Later legislation changes this provision in ways not yet written into the text below:

  • reg.3(1) (defn of British Standard Requirements) added reg.3(1) (defn of Institution Electrical Engineers Regs) revoked by Electricity Supply 1992 reg.2(a) of SI 2961, reg.2(b)
(1)

Subject to paragraph (2), and without prejudice to any other requirement as to earthing, any metalwork enclosing, supporting or otherwise associated with a supplier’s works and which is not intended to serve as a phase conductor shall, where necessary to prevent danger, be connected with earth.

(2)

Paragraph (1) shall not apply—

(a)

to any metalwork attached to, or forming part of, a wooden pole support the design and construction of which are such as to prevent, so far as is reasonably practicable, danger within three metres of the ground from any failure of insulation; or

(b)

to any wall-mounted metal bracket carrying an overhead line not connected with earth where the line is both supported by an insulator and the part of the line in contact with the insulator is itself surrounded by insulation.