  "heading": "Authorisation conditions: storage installations at terminals",
  "text": "SEPA must ensure that an authorisation for a petrol vapour recovery activity includes such conditions as it considers appropriate to ensure that storage installations at terminals comply with the following requirements—\n(a) the external wall and roof of tanks must, where above ground, be painted in a colour with a total radiant heat reflectance of 70% or more unless sub-paragraph (b) applies,\n(b) this sub-paragraph applies to a tank—\n(i) in, or visible from, a National Park or an area subject to local landscape designations,\n(ii) which is linked to a vapour recovery unit which conforms with the requirements set out in paragraph 6(3), (5) and (6),\n(c) requirements under sub-paragraph (a) may be carried out as part of the usual maintenance cycles of the tanks, provided that they are carried out at least every three years,\n(d) tanks with external floating roofs must be equipped with a primary seal to cover the annular space between the tank wall and the outer periphery of the floating roof, and with a secondary seal fitted above the primary seal,\n(e) seals referred to in sub-paragraph (d) should be designed to achieve an overall containment of vapours of 95% or more as compared to a comparable fixed-roof tank with no vapour-containment controls, which is a fixed-roof tank with only vacuum/pressure relief valve,\n(f) new storage installations at terminals where vapour recovery is required must be—\n(i) fitted with fixed-roof tanks connected to the vapour recovery unit in accordance with the requirements of paragraph 6(3), (5) and (6) of this schedule, or\n(ii) designed with a floating roof (either external or internal) equipped with primary and secondary seals to meet the performance requirements in sub-paragraph (d),\nunless sub-paragraph (h) applies,\n(g) existing fixed-roof tanks must—\n(i) be connected to a vapour-recovery unit as required for the purposes of paragraph 6(3), (5) and (6) of this schedule, or\n(ii) have an internal floating roof with a primary seal designed to achieve an overall containment of vapours of 90% or more in relation to a comparable fixed-roof tank with no vapour controls,\nunless sub-paragraph (h) applies,\n(h) the requirements for vapour-containment controls in sub-paragraphs (f) and (g) do not apply to fixed-roof tanks at terminals where intermediate storage of vapours is permitted according to paragraph 6(4) of this schedule.",
  "extent": null,
  "status": null,
  "version": "current",
  "annotations": [
    {
      "type": "F",
      "label": "F1",
      "text": "Sch. 28 inserted (1.11.2025) by The Environmental Authorisations (Scotland) Amendment Regulations 2025 (S.S.I. 2025/165), reg. 1(2), sch. 19 (with sch. 23)"
    }
  ],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/ssi/2018/219/schedule/28/paragraph/5",
    "retrieved_at": "2026-10-28T21:11:56.403037+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}