  "legislation_title": "Commission Decision of 3 May 2000 implementing Council Directive 89/106/EEC as regards the classification of the resistance to fire performance of construction products, construction works and parts thereof (notified under document number C(2000) 1001) (Text with EEA relevance) (2000/367/EC)",
  "legislation_url": "https://openlegislation.uk/eu-decision-2000-367",
  "path": "annex/division/2/division/4",
  "kind": "division",
  "number": "4",
  "heading": "Non-loadbearing elements or parts of works and products therefor",
  "text": "For cavity barriers this standard is complemented by EOTA TR 031.\nApplies to\npartitions (including partitions incorporating uninsulated portions, and cavity barriers)\nStandard(s)\nEN13501-2; EN 1364-1 ; EN 1992-1-2; EN 1993-1-2; EN 1994-1-2; EN 1995-1-2; EN 1996-1-2; EN 1999-1-2\nClassification: -\nE\n20\n30\n60\n90\n120\nEI\n15\n20\n30\n45\n60\n90\n120\n180\n240\nEI-M\n30\n60\n90\n120\n180\n240\nEW\n20\n30\n60\n90\n120\nNotes\n—\nApplies to\nceilings with independent fire resistance\nStandard(s)\nEN 13501-2; EN 1364-2\nClassification:\nEI\n15\n30\n45\n60\n90\n120\n180\n240\nNotes\nThe classification is completed by ‘(a → b)’, ‘(b → a)’, or ‘(a ↔ b)’ to indicate whether the element has been tested and fulfils the requirements from above or below only or both.\nApplies to\nfacades (curtain walls) and external walls (including glazed elements)\nStandard(s)\nEN 13501-2; EN 1364-3,4,5,6; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1996-1.2; EN 1999-1.2\nClassification:\nE\n15\n30\n60\n90\n120\nEI\n15\n30\n60\n90\n120\nEW\n20\n30\n60\nNotes\nThe classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both.\nWhere required, mechanical stability means that there are no falling parts liable to cause personal injury during the time for the E or EI classification.\nApplies to\nraised floors\nStandard(s)\nEN 13501-2; EN 1366-6\nClassification:\nR\n15\n30\nRE\n30\nREI\n30\nNotes\nThe classification is completed by the addition of the suffix ‘f’ to indicate full fire resistance or ‘r’ to indicate exposure to the reduced constant temperature exposure only.\nApplies to\npenetration seals and linear gap seals\nStandard(s)\nEN 13501-2; EN 1366-3,4\nClassification:\nE\n15\n30\n45\n60\n90\n120\n180\n240\nEI\n15\n20\n30\n45\n60\n90\n120\n180\n240\nNotes\n—\nThe ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.\nApplies to\nfire doors and shutters (including those that incorporate glazing and hardware) and their closing devices\nStandard(s)\nEN 13501-2; EN 1634-1\nClassification:\nE\n15\n20\n30\n45\n60\n90\n120\n180\n240\nEI\n15\n20\n30\n45\n60\n90\n120\n180\n240\nEW\n20\n30\n60\nNotes\nThe I classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) .\nThe ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.\nApplies to\nsmoke control doors\nStandard(s)\nEN 13501-2; EN 1634-3\nClassification: S200 or Sa depending upon the test conditions fulfilled\nNotes\nThe addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) .\nThe ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.\nApplies to\nclosures for conveyers and trackbound transportation systems\nStandard(s)\nEN 13501-2; EN 1366-7\nClassification:\nE\n15\n30\n45\n60\n90\n120\n180\n240\nEI\n15\n20\n30\n45\n60\n90\n120\n180\n240\nEW\n20\n30\n60\nNotes\nThe I classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. An I classification shall be generated for those cases where the test specimen is a pipe or duct configuration with no assessment of the closure for the conveyor system. The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) .\nApplies to\nservice ducts and shafts\nStandard(s)\nEN 13501-2; EN 1366-5\nClassification:\nE\n15\n20\n30\n45\n60\n90\n120\n180\n240\nEI\n15\n20\n30\n45\n60\n90\n120\n180\n240\nNotes\nThe classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbols ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use.\nApplies to\nchimneys\nStandard(s)\nEN 13501-2; EN 13216\nClassification: G + distance in mm (e.g. G 50)\nNotes\nDistance not required for built-in products.\nNotes\nThe suffixes ‘ 1 ’ and ‘ 2 ’ indicate which substrates, fire behaviour criteria and extension rules are used in this classification.\nApplies to\nWall and ceiling coverings\nStandard(s)\nEN 13501-2; EN 14135\nClassification:\nK 1\n10\nK 2\n10\n30\n60",
  "extent": "E+W+S+N.I.",
  "status": null,
  "version": "current",
  "annotations": [
    {
      "type": "F",
      "label": "F1",
      "text": "Substituted by Commission Decision of 11 April 2011 amending Decision 2000/367/EC establishing a classification system for resistance-to-fire performance for construction products, construction works and parts thereof (notified under document C(2011) 2417) (Text with EEA relevance) (2011/232/EU)."
    },
    {
      "type": "F",
      "label": "F2",
      "text": "Substituted by Commission Decision of 27 August 2003 amending Decision 2000/367/EC establishing a classification system for resistance-to-fire performance for construction products, as regards the inclusion of smoke and heat control products (notified under document number C(2003) 2851) (Text with EEA relevance) (2003/629/EC)."
    },
    {
      "type": "footnote",
      "label": "f1",
      "text": "For cavity barriers this standard is complemented by EOTA TR 031."
    },
    {
      "type": "footnote",
      "label": "f2",
      "text": "The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification."
    },
    {
      "type": "footnote",
      "label": "f3",
      "text": "The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification."
    },
    {
      "type": "footnote",
      "label": "f4",
      "text": "The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification."
    }
  ],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/eudn/2000/367/annex/division/2/division/4",
    "retrieved_at": "2026-11-01T15:18:49.486046+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}