# Commission Decision of 3 May 2000 implementing Council Directive 89/106/EEC as regards the classification of the resistance to fire performance of construction products, construction works and parts thereof (notified under document number C(2000) 1001) (Text with EEA relevance) (2000/367/EC), Division 4: Non-loadbearing elements or parts of works and products therefor

Extent: E+W+S+N.I.

For cavity barriers this standard is complemented by EOTA TR 031.
Applies to
partitions (including partitions incorporating uninsulated portions, and cavity barriers)
Standard(s)
EN13501-2; EN 1364-1 ; EN 1992-1-2; EN 1993-1-2; EN 1994-1-2; EN 1995-1-2; EN 1996-1-2; EN 1999-1-2
Classification: -
E
20
30
60
90
120
EI
15
20
30
45
60
90
120
180
240
EI-M
30
60
90
120
180
240
EW
20
30
60
90
120
Notes
—
Applies to
ceilings with independent fire resistance
Standard(s)
EN 13501-2; EN 1364-2
Classification:
EI
15
30
45
60
90
120
180
240
Notes
The classification is completed by ‘(a → b)’, ‘(b → a)’, or ‘(a ↔ b)’ to indicate whether the element has been tested and fulfils the requirements from above or below only or both.
Applies to
facades (curtain walls) and external walls (including glazed elements)
Standard(s)
EN 13501-2; EN 1364-3,4,5,6; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1996-1.2; EN 1999-1.2
Classification:
E
15
30
60
90
120
EI
15
30
60
90
120
EW
20
30
60
Notes
The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both.
Where required, mechanical stability means that there are no falling parts liable to cause personal injury during the time for the E or EI classification.
Applies to
raised floors
Standard(s)
EN 13501-2; EN 1366-6
Classification:
R
15
30
RE
30
REI
30
Notes
The classification is completed by the addition of the suffix ‘f’ to indicate full fire resistance or ‘r’ to indicate exposure to the reduced constant temperature exposure only.
Applies to
penetration seals and linear gap seals
Standard(s)
EN 13501-2; EN 1366-3,4
Classification:
E
15
30
45
60
90
120
180
240
EI
15
20
30
45
60
90
120
180
240
Notes
—
The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.
Applies to
fire doors and shutters (including those that incorporate glazing and hardware) and their closing devices
Standard(s)
EN 13501-2; EN 1634-1
Classification:
E
15
20
30
45
60
90
120
180
240
EI
15
20
30
45
60
90
120
180
240
EW
20
30
60
Notes
The I classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) .
The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.
Applies to
smoke control doors
Standard(s)
EN 13501-2; EN 1634-3
Classification: S200 or Sa depending upon the test conditions fulfilled
Notes
The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) .
The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification.
Applies to
closures for conveyers and trackbound transportation systems
Standard(s)
EN 13501-2; EN 1366-7
Classification:
E
15
30
45
60
90
120
180
240
EI
15
20
30
45
60
90
120
180
240
EW
20
30
60
Notes
The I classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. An I classification shall be generated for those cases where the test specimen is a pipe or duct configuration with no assessment of the closure for the conveyor system. The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) .
Applies to
service ducts and shafts
Standard(s)
EN 13501-2; EN 1366-5
Classification:
E
15
20
30
45
60
90
120
180
240
EI
15
20
30
45
60
90
120
180
240
Notes
The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbols ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use.
Applies to
chimneys
Standard(s)
EN 13501-2; EN 13216
Classification: G + distance in mm (e.g. G 50)
Notes
Distance not required for built-in products.
Notes
The suffixes ‘ 1 ’ and ‘ 2 ’ indicate which substrates, fire behaviour criteria and extension rules are used in this classification.
Applies to
Wall and ceiling coverings
Standard(s)
EN 13501-2; EN 14135
Classification:
K 1
10
K 2
10
30
60

---
Source: https://www.legislation.gov.uk/eudn/2000/367/annex/division/2/division/4 (the official version)
Page: https://openlegislation.uk/eu-decision-2000-367/annex/division-2/division-4