  "url": "https://openlegislation.uk/eu-decision-2000-367/annex/division-2/division-7",
  "json_url": "https://openlegislation.uk/eu-decision-2000-367/annex/division-2/division-7.json",
  "legislation": "eudn/2000/367",
  "legislation_title": "Commission Decision of 3 May 2000 implementing Council Directive 89/106/EEC as regards the classification of the resistance to fire performance of construction products, construction works and parts thereof (notified under document number C(2000) 1001) (Text with EEA relevance) (2000/367/EC)",
  "legislation_url": "https://openlegislation.uk/eu-decision-2000-367",
  "path": "annex/division/2/division/7",
  "kind": "division",
  "number": "7",
  "heading": "Products to be used in smoke and heat control systems",
  "text": "The standards cited in this section are under preparation and may be due to revision or upgrade.\nNotes\nThe classification is completed by the suffix ‘ single ’ to indicate suitability for single compartment use only.\nIn addition, the symbols, ‘v e ’ and/or ‘h o ’ indicate the suitability for vertical and/or horizontal use.\n‘S’ indicates a leakage rate of less than 5 m 3 /hr/m 2 (All ducts without an ‘S’ classification must have a leakage rate of less than 10 m 3 /hr/m 2 )\n‘ 500 ’ , ‘ 1 000 ’ , ‘ 1 500 ’ indicate the suitability for use up to these values of pressure, measured at ambient.\nApplies to\nSingle compartment smoke control ducts\nStandard(s)\nEN 13501-4; EN 1363-1, 2, 3; EN 1366-9 EN 12101-7\nClassification: —\nE 300\n30\n60\n90\n120\nE 600\n30\n60\n90\n120\nNotes\nThe classification is completed by the suffix ‘ multi ’ to indicate suitability for multi-compartment use.\nIn addition, the symbols ‘v e ’ and/or ‘h o ’ indicate the suitability for vertical and/or horizontal use.\n‘S’ indicates a leakage rate of less than 5 m 3 /hr/m 2 (All ducts without an ‘S’ classification must have a leakage rate of less than 10 m 3 /hr/m 2 )\n‘ 500 ’ , ‘ 1 000 ’ , ‘ 1 500 ’ indicate the suitability for use up to these values of pressure, measured at ambient.\nApplies to\nMulti-compartment fire resistant smoke control ducts\nStandard(s)\nEN 13501-4; EN 1363-1, 2, 3; EN 1366-8; EN 12101-7\nClassification: —\nEI\n30\n60\n90\n120\nNotes\nThe classification is completed by the suffix ‘ single ’ to indicate suitability for single compartment use.\n‘HOT 400/30’ (high operational temperature) indicates that the damper has the ability to be opened or closed during a period of 30 minutes under temperature conditions below 400 °C (to be used only with E 600 classification).\n‘v ed ’, ‘v ew ’‘v edw ’ and/or ‘h od ’, ‘h ow ’‘h odw ’ indicate the suitability for vertical and/or horizontal use, together with mounting in a duct or in a wall or both respectively.\n‘S’ indicates a leakage rate of less than 200 m 3 /hr/m 2 . All dampers without an ‘S’ classification must have a leakage rate of less than 360 m 3 /hr/m 2 . All damper less than 200 m 3 /hr/m 2 take this value, all dampers between 200 m 3 /hr/m 2 and 360 m 3 /hr/m 2 take the 360 m 3 /hr/m 2 value. Leakage rates are both at ambient and elevated temperatures.\n‘ 500 ’ , ‘ 1 000 ’ , ‘ 1 500 ’ indicates the suitability for use up to at these values of under pressure, measured at ambient.\n‘ AA ’ or ‘ MA ’ indicates automatic activation or manual intervention\n‘ i→o ’ , ‘ i ←o ’ , ‘ i ↔o ’ , indicates the performance criteria are satisfied from inside to outside, outside to inside or both respectively.\n‘C 300 ’, ‘C 10000 ’, ‘C mod ’ indicates the suitability of the damper for use in smoke control only systems combined smoke control and environmental systems, or modulating dampers used in combined smoke control and environmental systems respectively.\nApplies to\nSingle compartment smoke control dampers\nStandard(s)\nEN 13501-4; EN 1363-1, 3; EN 1366- 9, 10; EN 12101-8\nClassification: —\nE 300\n30\n60\n90\n120\nE 600\n30\n60\n90\n120\nNotes\nThe classification is completed by the suffix ‘ multi ’ to indicate suitability for multi-compartment use.\n‘ HOT 400/30 ’ (high operational temperature) indicates that the damper has the ability to be opened or closed during a period of 30 minutes under temperature conditions below 400 °C.\n‘v ed ’, ‘v ew ’‘v edw ’ and/or ‘h od ’, ‘h ow ’‘h odw ’ indicate the suitability for vertical and/or horizontal use, together with mounting in a duct or in a wall or both respectively.\n‘S’ indicates a leakage rate of less than 200 m 3 /hr/m 2 . All dampers without an ‘S’ classification must have a leakage rate of less than 360 m 3 /hr/m 2 . All damper less than 200 m 3 /hr/m 2 take this value, all dampers between 200 m 3 /hr/m 2 and 360 m 3 /hr/m 2 take the 360 m 3 /hr/m 2 value. Leakage rates are both at ambient and elevated temperatures.\n‘ 500 ’ , ‘ 1 000 ’ , ‘ 1 500 ’ indicates the suitability for use up to these values of pressure, measured at ambient.\n‘ AA ’ or ‘ MA ’ indicates automatic activation or manual intervention\n‘ i→o ’ , ‘ i ←o ’ , ‘ i ↔o ’ , indicates that the performance criteria are satisfied from inside to outside, outside to inside or both, respectively.\n‘C 300 ’, ‘C 10000 ’, ‘C mod ’ indicates the suitability of the damper for use in smoke control only systems, combined smoke control and environmental systems, or modulating dampers used in combined smoke control and environmental systems, respectively.\nApplies to\nMulti-compartment fire resistant smoke control dampers\nStandard(s)\nEN 13501-4; EN 1363-1, 2, 3; EN 1366-2, 8, 10; EN 12101-8\nClassification:\nEI\n30\n60\n90\n120\nE\n30\n60\n90\n120\nNotes\n‘A’ can be any time over 120 minutes.\nApplies to\nSmoke barriers\nStandard(s)\nEN 13501-4; EN 1363-1, 2; EN 12101-1\nClassification: D\nD 600\n30\n60\n90\n120\nA\nDH\n30\n60\n90\n120\nA\nNotes\nApplies to\nPowered smoke and heat exhaust ventilators (fans), connecting joints\nStandard(s)\nEN13501-4; EN 1363-1; EN 12101-3; ISO 834-1\nClassification: F\nF 200\n120\nF 300\n60\nF 400\n90\n120\nF 600\n60\nF 842\n30\nNotes\nWhere θ indicates the exposure condition (temperature).\nApplies to\nNatural smoke and heat exhaust ventilators\nStandard(s)\nEN 13501-4; EN 1363-1; EN 12101-2\nClassification: B\nB 300\n30\nB 600\n30\nB θ\n30",
  "extent": "E+W+S+N.I.",
  "status": null,
  "version": "current",
  "annotations": [
    {
      "type": "F",
      "label": "F1",
      "text": "Inserted by Commission Decision of 27 August 2003 amending Decision 2000/367/EC establishing a classification system for resistance-to-fire performance for construction products, as regards the inclusion of smoke and heat control products (notified under document number C(2003) 2851) (Text with EEA relevance) (2003/629/EC)."
    }
  ],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/eudn/2000/367/annex/division/2/division/7",
    "retrieved_at": "2026-11-01T15:18:49.486046+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}