  "url": "https://openlegislation.uk/eu-decision-2001-671/annex/division-2",
  "json_url": "https://openlegislation.uk/eu-decision-2001-671/annex/division-2.json",
  "legislation": "eudn/2001/671",
  "legislation_title": "Commission Decision of 21 August 2001 implementing Council Directive 89/106/EEC as regards the classification of the external fire performance of roofs and roof coverings (notified under document number C(2001) 2474) (Text with EEA relevance) (2001/671/EC)",
  "legislation_url": "https://openlegislation.uk/eu-decision-2001-671",
  "path": "annex/division/2",
  "kind": "division",
  "number": null,
  "heading": "SYMBOLS",
  "text": "The classifications according to the four test methods are identified as follows:\nENV 1187:2002 test 1: XROOF(t1), where t1 = Burning brand alone,\nENV 1187:2002 test 2: XROOF(t2), where t2 = Burning brand + wind,\nENV 1187:2002 test 3: XROOF(t3), where t3 = Burning brand + wind + radiation,\nENV 1187:2002 test 4: X ROOF (t4) where t4 = burning brand + wind + supplementary radiant heat.\nTE critical external fire spread time\nTP critical time to fire penetration\nTable\nCLASSES OF EXTERNAL FIRE PERFORMANCE FOR ROOFS/ROOF COVERINGS\nThe number of classes is still under review and will be amended as soon as the necessary information is available.\n* Attention shall be drawn to dripping from the underside of the specimen, any mechanical failure and any development of holes by adding a suffix “x” to the designation to denote that one or more of these took place during the test. In addition, depending upon inclination of the product during the test, the letters EXT.F will be added to indicate “flat or horizontal” and EXT.S will be added to indicate “inclined”.\nTest method\nClass\nClassification criteria\nCR1187:2001 test 1\nBROOF (t1)\nAll of the following conditions must be satisfied:\nexternal and internal fire spread upwards < 0,700 m,\nexternal and internal fire spread downwards < 0,600 m,\nmaximum burned length external and internal < 0,800 m,\nno burning material (droplets or debris) falling from exposed side,\nno burning/glowing particles penetrating the roof construction,\nno single through opening > 2,5 × 10–5 m2,\nsum of all through openings < 4,5 × 10–3 m2,\nlateral fire spread does not reach the edges of the measurement zone,\nno internal glowing combustion,\nmaximum redius of fire spread on ‘horizontal’, roofs, external and internal < 0,200 m.\nFROOF (t1)\nNo performance determined\nCR1187:2001 test 2\nBROOF (t2)\nFor both test series at 2 m/s and 4 m/s wind speed:\nmean damaged length of the roofing and underlay ≤ 0,550 m,\nmaximum damaged length of the roofing and underlay ≤ 0,800 m,\nFROOF (t2)\nNo performance determined\nCR1187:2001 test 3\nBROOF (t3)\nTE ≥ 30 min and TP ≥ 30 min\nCROOF (t3)\nTE ≥ 10 min and TP ≥ 15 min\nDROOF (t3)\nTP> 5 min\nFROOF (t3)\nNo performance determined\nENV 1187:2002 test 4\nB ROOF (t4)\nAll of the following conditions must be satisfied:\nNo penetration of roof system within 1 hour\nIn the preliminary test, after withdrawal of test flame, specimens burn for < 5 minutes\nIn the preliminary test, flame spread < 0.38 m across the region of burning\nC ROOF (t4)\nAll of the following conditions must be satisfied:\nNo penetration of roof system within 30 minutes\nIn the preliminary test, after withdrawal of test flame, specimens burn for < 5 minutes\nIn the preliminary test, flame spread < 0.38 m across the region of burning\nD ROOF (t4)\nAll of the following conditions must be satisfied:\nRoof system is penetrated within 30 minutes but is not penetrated in the preliminary flame test\nIn the preliminary test, after withdrawal of test flame, specimens burn for < 5 minutes\nIn the preliminary test, flame spread < 0.38 m across the region of burning\nE ROOF (t4)\nAll of the following conditions must be satisfied:\nRoof system is penetrated within 30 minutes but is not penetrated in the preliminary flame test\nFlame spread is not controlled\nF ROOF (t4)\nNo performance determined",
  "extent": "E+W+S+N.I.",
  "status": null,
  "version": "current",
  "annotations": [
    {
      "type": "F",
      "label": "F1",
      "text": "Substituted by Commission Decision of 22 November 2005 amending Decision 2001/671/EC implementing Council Directive 89/106/EEC as regards the classification of the external fire performance of roofs and roof coverings (notified under document number C(2005) 4437) (Text with EEA relevance) (2005/823/EC)."
    },
    {
      "type": "F",
      "label": "F2",
      "text": "Inserted by Commission Decision of 22 November 2005 amending Decision 2001/671/EC implementing Council Directive 89/106/EEC as regards the classification of the external fire performance of roofs and roof coverings (notified under document number C(2005) 4437) (Text with EEA relevance) (2005/823/EC)."
    },
    {
      "type": "footnote",
      "label": "f1",
      "text": "The number of classes is still under review and will be amended as soon as the necessary information is available."
    }
  ],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/eudn/2001/671/annex/division/2",
    "retrieved_at": "2026-11-01T15:18:39.775398+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}