  "url": "https://openlegislation.uk/eu-decision-2006-600/annex",
  "json_url": "https://openlegislation.uk/eu-decision-2006-600/annex.json",
  "legislation": "eudn/2006/600",
  "legislation_title": "Commission Decision of 4 September 2006 establishing the classes of external fire performance for certain construction products as regards double skin metal faced sandwich panels for roofs (notified under document number C(2006) 3883) (Text with EEA relevance) (2006/600/EC)",
  "legislation_url": "https://openlegislation.uk/eu-decision-2006-600",
  "path": "annex",
  "kind": "annex",
  "number": null,
  "heading": null,
  "text": "The table set out in this Annex lists the construction products which satisfy all of the requirements for the external fire performance without need for testing.\nTable\nCLASSES OF EXTERNAL FIRE PERFORMANCE FOR DOUBLE SKIN METAL FACED SANDWICH PANELS FOR ROOFS\nPanels with a profiled external metal facing incorporating:\nminimum thickness 0,4 mm for facings of steel and stainless steel;\nminimum thickness 0,9 mm for facings of aluminium;\nat each longitudinal joint between two panels an overlap of the external metal facing extending across the crown and a minimum 15 mm down the opposite face of the crown, or a metal cover cap completely covering the joint crown, or a raised standing metal seam along the joint;\nat each transverse joint between two panels an overlap of the external metal facing of at least 75 mm;\na protective weather coating comprising a liquid applied PVC paint of maximum nominal dry film thickness 0,200 mm, a PCS of not greater than 8,0 MJ/m2 and a maximum dry mass of 300 g/m2;\nor any thin paint coating less than the above;\nminimum reaction to fire classification of D-s3, d0 without edge protection in accordance with EN 13501-1.\nClass as provided for in the table of the Annex to Decision 2001/671/EC.\nSymbols used: PUR = polyurethane; MW = mineral wool; PVC = polyvinyl chloride; PCS = gross calorific potential.\nProduct\nProduct detail\nCore material with minimum density\nClass\nSteel, stainless steel or aluminium faced sandwich panels for roofs\nIn accordance with EN 14509\nPUR 35 kg/m3\nor\nBROOF (t1)\nMW (lamellas) 80 kg/m3\nor\nBROOF (t2)\nMW (full width boards) 110 kg/m3\nBROOF (t3)",
  "extent": "E+W+S+N.I.",
  "status": null,
  "version": "current",
  "annotations": [
    {
      "type": "footnote",
      "label": "f1",
      "text": "Panels with a profiled external metal facing incorporating: minimum thickness 0,4 mm for facings of steel and stainless steel; minimum thickness 0,9 mm for facings of aluminium; at each longitudinal joint between two panels an overlap of the external metal facing extending across the crown and a minimum 15 mm down the opposite face of the crown, or a metal cover cap completely covering the joint crown, or a raised standing metal seam along the joint; at each transverse joint between two panels an overlap of the external metal facing of at least 75 mm; a protective weather coating comprising a liquid applied PVC paint of maximum nominal dry film thickness 0,200 mm, a PCS of not greater than 8,0 MJ/m2 and a maximum dry mass of 300 g/m2; or any thin paint coating less than the above; minimum reaction to fire classification of D-s3, d0 without edge protection in accordance with EN 13501-1."
    },
    {
      "type": "footnote",
      "label": "f2",
      "text": "Class as provided for in the table of the Annex to Decision 2001/671/EC."
    }
  ],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/eudn/2006/600/annex",
    "retrieved_at": "2026-11-01T15:17:30.849297+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}