# Commission Decision of 15 May 2007 amending Decision 2003/43/EC establishing the classes of reaction-to-fire performance for certain construction products as regards wood-based panels (notified under document number C(2007) 2045) (Text with EEA relevance) (2007/348/EC), Annex

Extent: E+W+S+N.I.

In the Annex to Decision 2003/43/EC, Table 1 is replaced by the following:
‘
Table 1
Classes of reaction to fire performance for wood-based panels
Mounted without an air gap directly against class A1 or A2-s1, d0 products with minimum density 10 kg/m3 or at least class D-s2, d2 products with minimum density 400 kg/m3.
A substrate of cellulose insulation material of at least class E may be included if mounted directly against the wood-based panel, but not for floorings.
Mounted with an air gap behind. The reverse face of the cavity shall be at least class A2-s1, d0 products with minimum density 10 kg/m3.
Mounted with an air gap behind. The reverse face of the cavity shall be at least class D-s2, d2 products with minimum density 400 kg/m3.
Veneered, phenol- and melamine-faced panels are included for class excl. floorings.
A vapour barrier with a thickness up to 0,4 mm and a mass up to 200 g/m2 can be mounted in between the wood-based panel and a substrate if there are no air gaps in between.
Class as provided for in Table 1 of the Annex to Decision 2000/147/EC.
Class as provided for in Table 2 of the Annex to Decision 2000/147/EC.
Product
EN product standard
End use condition
Minimum density(kg/m3)
Minimum thickness(mm)
Class(excluding floorings)
Class(floorings)
Cement-bonded particleboard
EN 634-2
without an air gap behind the panel
1 000
10
B-s1, d0
Bfl-s1
Fibreboard, hard
EN 622-2
without an air gap behind the wood-based panel
900
6
D-s2, d0
Dfl-s1
Fibreboard, hard
EN 622-2
with a closed air gap not more than 22 mm behind the wood-based panel
900
6
D-s2, d2
—
Particleboard,,
EN 312
without an air gap behind the wood-based panel
600
9
D-s2, d0
Dfl-s1
Fibreboard, hard and medium,,
EN 622-2
EN 622-3
MDF,,
EN 622-5
MDF,,
EN 300
Plywood,,
EN 636
-“-
400
9
D-s2, d0
Dfl-s1
Solid wood panel,,
EN 13353
12
Flaxboard,,
EN 15197
-“-
450
15
D-s2, d0
Dfl-s1
Particleboard,
EN 312
with a closed or an open air gap not more than 22 mm behind the wood-based panel
600
9
D-s2, d2
—
Fibreboard, hard and medium,
EN 622-2
EN 622-3
MDF,
EN 622-5
OSB,
EN 300
Plywood,
EN 636
-“-
400
9
D-s2, d2
—
Solid wood panel,
EN 13353
12
Particleboard,
EN 312
with a closed air gap behind the wood-based panel
600
15
D-s2, d0
Dfl-s1
Fibreboard, medium,
EN 622-3
MDF,
EN 622-5
OSB,
EN 300
Plywood,
EN 636
-“-
400
15
D-s2, d1
Dfl-s1
Solid wood panel,
EN 13353
D-s2, d0
Flaxboard,
EN 15197
-“-
450
15
D-s2, d0
Dfl-s1
Particleboard,
EN 312
with an open air gap behind the wood-based panel
600
18
D-s2, d0
Dfl-s1
Fibreboard, medium,
EN 622-3
MDF,
EN 622-5
OSB,
EN 300
Plywood,
EN 636
-“-
400
18
D-s2, d0
Dfl-s1
Solid wood panel,
EN 13353
Flaxboard,
EN 15197
-“-
450
18
D-s2, d0
Dfl-s1
Particleboard
EN 312
any
600
3
E
Efl
OSB
EN 300
MDF
EN 622-5
-“-
400
3
E
Efl
250
9
E
Efl
Plywood
EN 636
-“-
400
3
E
Efl
Fibreboard, hard
EN 622-2
-“-
900
3
E
Efl
Fibreboard, medium
EN 622-3
-“-
400
9
E
Efl
Fibreboard, soft
EN 622-4
-“-
250
9
E
Efl
’

---