{
  "url": "https://openlegislation.uk/eu-decision-2007-742/annex/division-2",
  "json_url": "https://openlegislation.uk/eu-decision-2007-742/annex/division-2.json",
  "legislation": "eudn/2007/742",
  "legislation_title": "Commission Decision of 9 November 2007 establishing the ecological criteria for the award of the Community eco-label to electrically driven, gas driven or gas absorption heat pumps (notified under document number C(2007) 5492) (Text with EEA relevance) (2007/742/EC)",
  "legislation_url": "https://openlegislation.uk/eu-decision-2007-742",
  "path": "annex/division/2",
  "kind": "division",
  "number": "2",
  "heading": "Efficiency in cooling mode (EER)",
  "text": "If the heat pump is reversible and can cool, then the efficiency of the heat pump unit shall exceed the following minimum requirements of the energy efficiency ratio (EER) in cooling mode.\nType of heat pump:\nOutdoor unit [°C]\nIndoor unit [°C]\nMin. EER\nMin. EER\nMin. PER\nElectric heat pump\nGas heat pump\nair/air\nInlet dry bulb: 35\nInlet wet bulb: 24\nInlet dry bulb: 27\nInlet wet bulb: 19\n3,2\n1,41\n1,3\nair/water\nInlet dry bulb: 35\nInlet wet bulb: —\nInlet temperature: 23\nOutlet temperature: 18\n2,2\n0,97\n0,9\nInlet temperature: 12\nOutlet temperature: 7\n2,2\n0,97\n0,9\nbrine/air\nInlet temp: 30\nOutlet temp: 35\nInlet dry bulb: 27\nInlet wet bulb: 19 max\n3,3\n1,45\n1,3\nbrine/water\nInlet temp: 30\nOutlet temp: 35\nInlet temperature: 23\nOutlet temperature: 18\n3,0\n1,32\n1,2\nInlet temperature: 12\nOutlet temperature: 7\n3,0\n1,32\n1,2\nwater/water\nInlet temp: 30\nOutlet temp: 35\nInlet temperature: 23\nOutlet temperature: 18\n3,2\n1,41\n1,3\nInlet temperature: 12\nOutlet temperature: 7\n3,2\n1,41\n1,3\nwater/air\nInlet temp: 30\nOutlet temp: 35\nInlet dry bulb: 27\nInlet wet bulb: 19\n4,4\n1,93\n1,8\nAssessment and verification: Testing shall be performed in accordance to EN 14 511:2004; for gas absorption heat pumps in accordance with EN12309-2:2000. The test shall be performed at the full capacity of the heat pump in question, at the conditions specified in the table. An independent test laboratory accredited for the stated testing shall verify the given values. Heat pumps which are certified in the Eurovent certification programme or DACH certification programme, or another programme approved by the competent body, do not require additional testing by an independent laboratory for the given values. The test reports shall be submitted with the application.",
  "extent": "E+W+S+N.I.",
  "status": null,
  "version": "current",
  "annotations": [],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/eudn/2007/742/annex/division/2",
    "retrieved_at": "2026-11-01T15:17:02.326248+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}