# Commission Decision of 1 March 2013 establishing the guidelines for Member States on calculating renewable energy from heat pumps from different heat pump technologies pursuant to Article 5 of Directive 2009/28/EC of the European Parliament and of the Council (notified under document C(2013) 1082) (Text with EEA relevance) (2013/114/EU), Division 3.6: Default values for SPF and Qusable for heat pumps

Extent: E+W+S+N.I.

The default values for HHP and SPF (SCOPnet) for electrically driven heat pumps are as set out in the table below:
Table 1
Default values for HHP and SPF (SCOPnet) for electrically driven heat pumps
Climate conditions
Warmer climate
Average climate
Colder climate
Heat Pump Energy source:
Energy source and distribution medium
HHP
SPF(SCOPnet)
HHP
SPF(SCOPnet)
HHP
SPF(SCOPnet)
Aerothermal energy
Air-Air
1 200
2,7
1 770
2,6
1 970
2,5
Air-Water
1 170
2,7
1 640
2,6
1 710
2,5
Air-Air (reversible)
120
2,7
710
2,6
1 970
2,5
Air-Water (reversible)
120
2,7
660
2,6
1 710
2,5
Exhaust Air-Air
760
2,7
660
2,6
600
2,5
Exhaust Air-Water
760
2,7
660
2,6
600
2,5
Geothermal energy
Ground-Air
1 340
3,2
2 070
3,2
2 470
3,2
Ground-Water
1 340
3,5
2 070
3,5
2 470
3,5
Hydrothermal heat
Water-Air
1 340
3,2
2 070
3,2
2 470
3,2
Water-Water
1 340
3,5
2 070
3,5
2 470
3,5
The default values for HHP and SPF (SPERnet) for heat pumps driven by thermal energy are as set out in the table below:
Table 2
Default values for HHP and SPF (SPERnet) for heat pumps driven by thermal energy
Climate conditions
Warmer climate
Average climate
Colder climate
Heat Pump Energy source:
Energy source and distribution medium
HHP
SPF(SPERnet)
HHP
SPF(SPERnet)
HHP
SPF(SPERnet)
Aerothermal energy
Air-Air
1 200
1,2
1 770
1,2
1 970
1,15
Air-Water
1 170
1,2
1 640
1,2
1 710
1,15
Air-Air (reversible)
120
1,2
710
1,2
1 970
1,15
Air-Water (reversible)
120
1,2
660
1,2
1 710
1,15
Exhaust Air-Air
760
1,2
660
1,2
600
1,15
Exhaust Air-Water
760
1,2
660
1,2
600
1,15
Geothermal energy
Ground-Air
1 340
1,4
2 070
1,4
2 470
1,4
Ground-Water
1 340
1,6
2 070
1,6
2 470
1,6
Hydrothermal heat
Water-Air
1 340
1,4
2 070
1,4
2 470
1,4
Water-Water
1 340
1,6
2 070
1,6
2 470
1,6
The default values set out in Tables 1 and 2 above are typical for the segment of heat pumps with a SPF above the minimum threshold, meaning that heat pumps with SPF below 2,5 have not been taken into consideration when the typical values have been established.

---
Source: https://www.legislation.gov.uk/eudn/2013/114/annex/division/3/division/3.6 (the official version)
Page: https://openlegislation.uk/eu-decision-2013-114/annex/division-3/division-3.6