  "legislation_title": "Commission Decision of 1 March 2013 establishing the guidelines for Member States on calculating renewable energy from heat pumps from different heat pump technologies pursuant to Article 5 of Directive 2009/28/EC of the European Parliament and of the Council (notified under document C(2013) 1082) (Text with EEA relevance) (2013/114/EU)",
  "legislation_url": "https://openlegislation.uk/eu-decision-2013-114",
  "path": "annex/division/4",
  "kind": "division",
  "number": "4",
  "heading": "CALCULATION EXAMPLE",
  "text": "The table below show an example for a hypothetical Member State located in average climate conditions, which has 3 different heat pump technologies installed.\nThe Member State in this hypothetical example did a survey of installed reversible air to air heat pumps and concluded that the equivalent of 48 % of the installed reversible heat pump capacity were used fully for heating, instead of the 40 % assumed in these guidelines. The HHP value is therefore adjusted up from 710 hours, which assumes 40 % and set out in Table 1, to 852 hours, which is representative for the estimated 48 %.\nAir to air(reversible)\nWater to water\nExhaust Air to water\nCalculation\nDescription\nVariable\nUnit\nCapacity of heat pumps installed\nPrated\nGW\n255\n74\n215\nof which the SPF is above the minimum threshold\nPrated\nGW\n150\n70\n120\nEquivalent full load hours of operation\nHHP\nh\n852\n2 070\n660\nP rated * H HP = Q usable\nEstimated total usable heat delivered by heat pumps\nQusable\nGWh\n127 800\n144 900\n79 200\nthe estimated average seasonal performance factor\nSPF\n2,6\n3,5\n2,6\nE RES = Q usable 1 − 1 ∕ SPF\nAmount of renewable energy supplied per heat pump technology\nERES\nGWh\n78 646\n103 500\n48 738\nTotal amount of renewable energy supplied by heat pumps\nERES\nGWh\n230 885",
  "extent": "E+W+S+N.I.",
  "status": null,
  "version": "current",
  "annotations": [
    {
      "type": "X",
      "label": "X1",
      "text": "Substituted by Corrigendum to Commission Decision 2013/114/EU of 1 March 2013 establishing the guidelines for Member States on calculating renewable energy from heat pumps from different heat pump technologies pursuant to Article 5 of Directive 2009/28/EC of the European Parliament and of the Council (Official Journal of the European Union L 62 of 6 March 2013)."
    },
    {
      "type": "footnote",
      "label": "f1",
      "text": "The Member State in this hypothetical example did a survey of installed reversible air to air heat pumps and concluded that the equivalent of 48 % of the installed reversible heat pump capacity were used fully for heating, instead of the 40 % assumed in these guidelines. The HHP value is therefore adjusted up from 710 hours, which assumes 40 % and set out in Table 1, to 852 hours, which is representative for the estimated 48 %."
    }
  ],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/eudn/2013/114/annex/division/4",
    "retrieved_at": "2026-11-01T15:15:09.548273+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}