# Commission Decision of 1 March 2013 establishing the guidelines for Member States on calculating renewable energy from heat pumps from different heat pump technologies pursuant to Article 5 of Directive 2009/28/EC of the European Parliament and of the Council (notified under document C(2013) 1082) (Text with EEA relevance) (2013/114/EU), Division 4: CALCULATION EXAMPLE

Extent: E+W+S+N.I.

The table below show an example for a hypothetical Member State located in average climate conditions, which has 3 different heat pump technologies installed.
The Member State in this hypothetical example did a survey of installed reversible air to air heat pumps and concluded that the equivalent of 48 % of the installed reversible heat pump capacity were used fully for heating, instead of the 40 % assumed in these guidelines. The HHP value is therefore adjusted up from 710 hours, which assumes 40 % and set out in Table 1, to 852 hours, which is representative for the estimated 48 %.
Air to air(reversible)
Water to water
Exhaust Air to water
Calculation
Description
Variable
Unit
Capacity of heat pumps installed
Prated
GW
255
74
215
of which the SPF is above the minimum threshold
Prated
GW
150
70
120
Equivalent full load hours of operation
HHP
h
852
2 070
660
P rated * H HP = Q usable
Estimated total usable heat delivered by heat pumps
Qusable
GWh
127 800
144 900
79 200
the estimated average seasonal performance factor
SPF
2,6
3,5
2,6
E RES = Q usable 1 − 1 ∕ SPF
Amount of renewable energy supplied per heat pump technology
ERES
GWh
78 646
103 500
48 738
Total amount of renewable energy supplied by heat pumps
ERES
GWh
230 885

---
Source: https://www.legislation.gov.uk/eudn/2013/114/annex/division/4 (the official version)