  "url": "https://openlegislation.uk/eu-decision-2016-902/annex/division-3/division-5/division-5.3",
  "json_url": "https://openlegislation.uk/eu-decision-2016-902/annex/division-3/division-5/division-5.3.json",
  "legislation": "eudn/2016/902",
  "legislation_title": "Commission Implementing Decision (EU) 2016/902 of 30 May 2016 establishing best available techniques (BAT) conclusions, under Directive 2010/75/EU of the European Parliament and of the Council, for common waste water and waste gas treatment/management systems in the chemical sector (notified under document C(2016) 3127) (Text with EEA relevance)",
  "legislation_url": "https://openlegislation.uk/eu-decision-2016-902",
  "path": "annex/division/3/division/5/division/5.3",
  "kind": "division",
  "number": "5.3",
  "heading": "Flaring",
  "text": "Technique\nDescription\nApplicability\n(a)\nCorrect plant design\nThis includes the provision of a gas recovery system with sufficient capacity and the use of high-integrity relief valves.\nGenerally applicable to new plants. Gas recovery systems may be retrofitted in existing plants.\n(b)\nPlant management\nThis includes balancing the fuel gas system and using advanced process control.\nGenerally applicable.\nTechnique\nDescription\nApplicability\n(a)\nCorrect design of flaring devices\nOptimisation of height, pressure, assistance by steam, air or gas, type of flare tips (either enclosed or shielded), etc., aimed to enable smokeless and reliable operation and to ensure the efficient combustion of excess gases.\nApplicable to new flares. In existing plants, applicability may be restricted due to e.g. maintenance time availability during the turnaround of the plant.\n(b)\nMonitoring and recording as part of flare management\nContinuous monitoring of the gas sent to flaring, measurements of gas flow and estimations of other parameters (e.g. composition, heat content, ratio of assistance, velocity, purge gas flow rate, pollutant emissions (e.g. NOX, CO, hydrocarbons, noise)). The recording of flaring events usually includes the estimated/measured flare gas composition, the estimated/measured flare gas quantity and the duration of operation. The recording allows for the quantification of emissions and the potential prevention of future flaring events.\nGenerally applicable.",
  "extent": "E+W+S+N.I.",
  "status": null,
  "version": "current",
  "annotations": [],
  "outstanding_effects": [],
  "provenance": {
    "source": "legislation.gov.uk",
    "source_url": "https://www.legislation.gov.uk/eudn/2016/902/annex/division/3/division/5/division/5.3",
    "retrieved_at": "2026-11-01T15:13:57.064168+00:00"
  },
  "licence": "Open Government Licence v3.0",
  "licence_url": "https://www.nationalarchives.gov.uk/doc/open-government-licence/version/3/",
  "attribution": "Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives."
}