OpenLegislation

Division Regulation 2: DefinitionsF1

United Kingdom

Original text. Later amendments are not shown.

Paragraph (2) ‘ standard fire test ’ to be read with the following changes at the end with regard to the standard temperature curve:

‘ … The standard time-temperature curve is defined by a smooth curve drawn through the following internal furnace temperature points:

— initial internal furnace temperature: 20 °C
— at the end of the first five minutes: 576 °C
— at the end of 10 minutes: 679 °C
— at the end of 15 minutes: 738 °C
— at the end of 30 minutes: 841 °C
— at the end of 60 minutes: 945 °C

’

Annotations

Textual amendments

F1

Substituted by Commission Directive 2002/35/EC of 25 April 2002 amending Council Directive 97/70/EC setting up a harmonised safety regime for fishing vessels of 24 metres in length and over (Text with EEA relevance).