Division .1.2 Maintenance, testing and inspectionsF1
United Kingdom
Maintenance, testing and inspections shall be carried out based on the guidelines in IMO MSC/Circ.850 and in a manner having due regard to ensuring the reliability of fire-fighting systems and appliances. A maintenance plan shall be kept on board the ship and shall be available for inspection, whenever required by the Administration of the flag State.
The maintenance plan shall include at least the following fire protection systems and fire-fighting systems and appliances, where installed:
- .1
fire mains, fire pumps and hydrants including hoses and nozzles;
- .2
fixed fire detection and fire alarm systems;
- .3
fixed fire-extinguishing systems and other fire-extinguishing appliances;
- .4
automatic sprinkler, fire detection and fire alarm systems;
- .5
ventilation systems including fire and smoke dampers, fans and their controls;
- .6
emergency shut down of fuel supply;
- .7
fire doors including their controls;
- .8
general emergency alarm systems;
- .9
emergency escape breathing devices;
- .10
portable fire extinguishers including spare charges; and
- .11
firefighter’s outfits.
The maintenance programme may be computer-based.