A standard fire test is one in which specimens of the relevant bulkheads or decks are exposed in a test furnace to temperatures corresponding approximately to the standard time-temperature curve. The specimen shall have an exposed surface of not less than 4,65 m 2 and height (or length of deck) of 2,44 metres, resembling as closely as possible the intended construction and including where appropriate at least one joint. The standard time-temperature curve is defined by a smooth curve drawn through the following internal furnace temperature points:

initial internal furnace temperature 20 °C
at the end of the first 5 minutes 576 °C
at the end of 10 minutes 679 °C
at the end of 15 minutes 738 °C
at the end of 30 minutes 841 °C
at the end of 60 minutes 945 °C