.1 in accommodation and service spaces:
the fire extinguishers shall be so located that no point in the space is more than 10 metres walking distance from an extinguisher;
.2 an extinguisher suitable for use in high voltage areas shall be located in the proximity of any electric panel or subpanel having a power of 20 kW or more;
.3 in galleys the extinguishers shall be so located that no point in the space is more than 10 metres walking distance from an extinguisher;
.4 an extinguisher shall be located in the proximity of paint lockers store rooms containing readily flammable products;
.5 at least one extinguisher shall be located on the navigating bridge and in each control station.

---