# Directive 2009/45/EC of the European Parliament and of the Council of 6 May 2009 on safety rules and standards for passenger ships (Recast) (Text with EEA relevance), Division .15: Fire detection systems with a zone address identification capability shall be so arranged that:

Extent: E+W+S+N.I.

a loop cannot be damaged at more than one point by a fire,
means are provided to ensure that any fault (e.g. power break, short circuit, earth) occurring in the loop will not render the whole loop ineffective,
all arrangements are made to enable the initial configuration of the system to be restored in the event of failure (electrical, electronic, informatic),
the first initiated fire alarm will not prevent any other detector to initiate further fire alarms.

---