# Directive 2009/45/EC of the European Parliament and of the Council of 6 May 2009 on safety rules and standards for passenger ships (Recast) (Text with EEA relevance), Division .4

Extent: E+W+S+N.I.

Detectors shall be located for optimum performance. Positions near beams and ventilation ducts or other positions where patterns of airflow could adversely affect performance and positions where impact or physical damage is likely, shall be avoided. In general, detectors which are located on the overhead shall be a minimum distance of 0,5 metres away from bulkheads.

---
Source: https://www.legislation.gov.uk/eudr/2009/45/annex/I/chapter/3/part/A/division/9/division/1/division/.2/division/.4 (the official version)