# Directive 2009/45/EC of the European Parliament and of the Council of 6 May 2009 on safety rules and standards for passenger ships (Recast) (Text with EEA relevance), Division .5: The maximum spacing of detectors shall be in accordance with the table below:

Extent: E+W+S+N.I.

Type of detector
Maximum floor area per detector (m 2 )
Maximum distance apart between centres (m)
Maximum distance away from bulkheads (m)
Heat
37
9
4,5
Smoke
74
11
5,5
The Administration of the flag State may require or permit other spaces based upon test data which demonstrate the characteristics of the detectors.

---