Division .2 Ships carrying more than 36 passengers, except ships with a length of less than 24 metres, shall be equipped with:F1
United Kingdom
An automatic sprinkler, fire detection and fire alarm system of an approved type complying with the requirements of Regulation II-2/A/8 or with the IMO guidelines for an approved equivalent sprinkler system as given in IMO Resolution A.800(19), in all service spaces, control stations and accommodation spaces, including corridors and stairways.
Alternatively control stations where water may cause damage to essential equipment may be fitted with an approved fixed fire-extinguishing system of another type.
A fixed fire detection and fire alarm system of an approved type, complying with the requirements of Regulation II-2/A/9 shall be installed, so installed and arranged as to provide smoke detection in service spaces, control stations and accommodation spaces, including corridors and stairways. Smoke detectors need not be fitted in private bathrooms and galleys.
Spaces having little or no fire risk such as voids, public toilets, carbon dioxide rooms and similar spaces need not be fitted with an automatic sprinkler system or fixed fire detection and alarm system.