# Directive 2009/45/EC of the European Parliament and of the Council of 6 May 2009 on safety rules and standards for passenger ships (Recast) (Text with EEA relevance), Division .6: With regard to the fixed fire detection and fire alarm system required by Regulations II-2/B/13.4 and 13.5, the following shall apply:

Extent: E+W+S+N.I.

The fire detection system shall be so designed and the detectors so positioned as to detect rapidly the onset of fire in any part of those spaces and under any normal conditions of operation of the machinery and variations of ventilation as required by the possible range of ambient temperatures. Except in spaces of restricted height and where their use is especially appropriate, detection systems using only thermal detectors shall not be permitted. The detection system shall initiate audible and visual alarms distinct in both respects from the alarms of any other system not indicating fire, in sufficient places to ensure that the alarms are heard and observed on the navigating bridge and by a responsible engineer officer.
When the navigating bridge is unmanned, the alarm shall sound in a place where a responsible member of the crew is on duty.
After installation, the system shall be tested under varying conditions of engine operation and ventilation.

---
Source: https://www.legislation.gov.uk/eudr/2009/45/annex/I/chapter/3/part/B/division/13/division/2/division/.6 (the official version)
Page: https://openlegislation.uk/eu-directive-2009-45/annex-I/chapter-3/part-B/division-13/division-2/division-.6
Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives.

