# Directive 2009/45/EC of the European Parliament and of the Council of 6 May 2009 on safety rules and standards for passenger ships (Recast) (Text with EEA relevance), Division .3: Fixed fire-extinguishing system

Extent: E+W+S+N.I.

Each special category space shall be fitted with an approved fixed pressure water-spraying system for manual operation which shall protect all parts of any deck and vehicle platform in such space.
In new class B, C and D ships constructed on or after 1 January 2003 , such water spray systems shall have:
.1 a pressure gauge on the valve manifold;
.2 clear marking on each manifold valve indicating the spaces served;
.3 instructions for maintenance and operation located in the valve room; and
.4 a sufficient number of drainage valves.
The Administration of the flag State may permit the use of any other fixed fire-extinguishing system that has been shown by full-scale test in conditions simulating a flowing petrol fire in a special category space to be not less effective in controlling fires likely to occur in such a space. Such fixed pressure water-spraying system or other equivalent fire-extinguishing system shall comply with the provisions of IMO Resolution A.123(V) and the IMO MSC/Circ.1272 ‘ Guidelines when approving alternative water-based fire-fighting systems for use in special category spaces ’ shall be taken into consideration.

---
Source: https://www.legislation.gov.uk/eudr/2009/45/annex/I/chapter/3/part/B/division/14/division/.1/division/1/division/.3 (the official version)
Page: https://openlegislation.uk/eu-directive-2009-45/annex-I/chapter-3/part-B/division-14/division-.1/division-1/division-.3
Contains public sector information licensed under the Open Government Licence v3.0. Source: legislation.gov.uk, The National Archives.