# Directive 2009/45/EC of the European Parliament and of the Council of 6 May 2009 on safety rules and standards for passenger ships (Recast) (Text with EEA relevance), Division .2: The following requirements shall govern application of the tables:

Extent: E+W+S+N.I.

.1 Tables 5.1 and 5.2 shall apply respectively to the bulkheads and decks separating adjacent spaces.
.2 For determining the appropriate fire integrity standards to be applied to divisions between adjacent spaces, such spaces are classified according to their fire risk as shown in categories (1) to (11) below. The title of each category is intended to be typical rather than restrictive. The number in parentheses preceding each category refers to the applicable column or row in the tables.
(1) Control stations:
spaces containing emergency sources of power and lighting,
wheelhouse and chartroom,
spaces containing the ship’s radio equipment,
fire-extinguishing rooms, fire control rooms and fire-recording stations,
control room for propulsion machinery when located outside the propulsion machinery space,
spaces containing centralised fire alarm equipment.
(2) Corridors:
passenger and crew corridors and lobbies.
(3) Accommodation spaces:
spaces as defined in Regulation II-2/A/2.10 excluding corridors.
(4) Stairways:
interior stairways, lifts and escalators (other than those wholly contained within the machinery spaces) and enclosures thereto,
in this connection, a stairway which is enclosed only at one level shall be regarded as part of the space from which it is not separated by a fire door.
(5) Service spaces (low risk):
lockers and storerooms not having provisions for the storage of flammable liquids and having areas less than 4 m 2 and drying rooms and laundries.
(6) Machinery spaces of category A:
spaces as defined in Regulation II-2/A/2.19.1.
(7) Other machinery spaces:
spaces as defined in Regulation II-2/A/2.19.2 excluding machinery spaces of category A.
(8) Cargo spaces:
all spaces used for cargo (including cargo oil tanks) and trunkways and hatchways to such spaces, other than special category spaces.
(9) Service spaces (high risk):
galleys, pantries containing cooking appliances, paint and lamp rooms, lockers and storerooms having areas of 4 m 2 or more, spaces for the storage of flammable liquids, and workshops other than those forming part of the machinery spaces.
(10) Open decks:
open deck spaces and enclosed promenades having no fire risk. Air spaces (the space outside superstructures and deckhouses).
(11) Special category spaces:
spaces as defined in Regulation II-2/A/2.18.
.3 In determining the applicable fire integrity standard of a boundary between two spaces within a main vertical zone or horizontal zone which is not protected by an automatic sprinkler system complying with the provisions of Regulation II-2/A/8 or between such zones neither of which is so protected, the higher of the two values given in the tables shall apply.
.4 In determining the applicable fire integrity standard of a boundary between two spaces within a main vertical zone or horizontal zone which is protected by an automatic sprinkler system complying with the provisions of Regulation II-2/A/8 or between such zones both of which are so protected, the lesser of the two values given in the tables shall apply. Where a sprinklered zone and a non-sprinklered zone meet within accommodation and service spaces, the higher of the two values given in the tables shall apply to the division between the zones.

---