# Directive 2009/45/EC of the European Parliament and of the Council of 6 May 2009 on safety rules and standards for passenger ships (Recast) (Text with EEA relevance), Division .3

Extent: E+W+S+N.I.

Where ventilation systems penetrate decks, precautions shall be taken, in addition to those relating to fire integrity of the deck required by Regulation II-2/A/12.1, to reduce the likelihood of smoke and hot gases passing from one between-deck space to another through the system. In addition to insulation requirements contained in this Regulation, vertical ducts shall, if necessary, be insulated as required by the appropriate tables in Regulation 4.

---