Ventilation ducts shall be constructed of the following materials:
.1 ducts not less than 0,075 m 2 in sectional area and all vertical ducts serving more than a single between-deck space shall be constructed of steel or other equivalent material;
.2 ducts less than 0,075 m 2 in sectional area other than vertical ducts referred to in subparagraph .1.4.1 shall be constructed of non-combustible materials. Where such ducts penetrate ‘A’ or ‘B’ class divisions due regard shall be given to ensuring the fire integrity of the division;
.3 short lengths of duct, not in general exceeding 0,02 m 2 in sectional area nor two metres in length, need not be non-combustible provided that all of the following conditions are met:
.1 the duct is constructed of a material of low fire risk to the satisfaction of the Administration of the flag State;
.2 the duct is used only at the terminal end of the ventilation system; and
.3 the duct is not located closer than 600 mm measured along its length to a penetration of an ‘ A ’ or ‘ B ’ class division, including continuous ‘ B ’ class ceilings.

---