Division .9 Exhaust ducts from galley ranges in which grease or fat is likely to accumulate shall meet requirements of subparagraphs .9.2.3.2.1 and .9.2.3.2.2 and shall be fitted with:F1
United Kingdom
- .1
a grease trap readily removable for cleaning unless an alternative approved grease removal system is fitted;
- .2
a fire damper located in the lower end of the duct which is automatically and remotely operated, and in addition a remotely operated fire damper located in the upper end of the duct;
- .3
a fixed means for extinguishing a fire within the duct;
- .4
remote control arrangements for shutting off the exhaust fans and supply fans, for operating the fire dampers mentioned in .2 and for operating the fire-extinguishing system, which shall be placed in a position close to the entrance to the galley. Where a multi-branch system is installed, means shall be provided to close all branches exhausting through the same main duct before an extinguishing medium is released into the system; and
- .5
suitably located hatches for inspection and cleaning.