# Directive 2009/45/EC of the European Parliament and of the Council of 6 May 2009 on safety rules and standards for passenger ships (Recast) (Text with EEA relevance), Division .1

Extent: E+W+S+N.I.

Ventilation ducts shall be of non-combustible material. Short ducts, however, not generally exceeding two metres in length and with a cross-section not exceeding 0,02 m 2 need not be non-combustible, subject to the following conditions:
.1 these ducts shall be of a material which, in the opinion of the Administration of the flag State, has a low fire risk;
.2 they may only be used at the end of the ventilation device;
.3 they shall not be situated less than 600 mm, measured along the duct, from an opening in an ‘ A ’ or ‘ B ’ class division, including continuous ‘ B ’ class ceilings.

---