Division .1 In addition to the requirements in sections .1, .2 and .3, the ventilation system of a passenger ship carrying more than 36 passengers shall also meet the following requirements:F1F2
United Kingdom
- .1
In general, the ventilation fans shall be so arranged that the ducts reaching the various spaces remain within a main vertical zone.
- .2
Stairway enclosures shall be served by an independent ventilation fan and duct system (exhaust and supply) which shall not serve any other spaces in the ventilation systems.
- .3
A duct, irrespective of its cross-section, serving more than one ‘ tween-deck ’ accommodation space, service space or control station, shall be fitted, near the penetration of each deck of such spaces, with an automatic smoke damper that shall also be capable of being closed manually from the protected deck above the damper. Where a fan serves more than one ‘ tween-deck ’ space through separate ducts within a main vertical zone, whereby each one is dedicated to a single ‘ tween-deck ’ space, each duct shall be provided with a manually operated smoke damper fitted close to the fan.
- .4
Vertical ducts shall, where necessary, be insulated as required by tables 4.1 and 4.2. Ducts shall be insulated as required for decks between the space they serve and the space being considered, as applicable.