Division .2 Requirements for passenger ships carrying not more than 36 passengersF1F2
United Kingdom
When passing through accommodation spaces or spaces containing combustible materials, the exhaust ducts from galley ranges shall be constructed in accordance with paragraphs .2.4.1.1 and .2.4.1.2. Each exhaust duct shall be fitted with:
- .1
a grease trap readily removable for cleaning;
- .2
an automatically and remotely operated fire damper located in the lower end of the duct at the junction between the duct and the galley range hood and, in addition, a remotely operated fire damper in the upper end of the duct close to the outlet of the duct;
- .3
arrangements, operable from within the galley, for shutting off the exhaust and supply fans; and
- .4
fixed means for extinguishing a fire within the duct.
Annotations
Textual amendments
- F1
- F2