Emission limit values (mg/Nm3) for SO2 for combustion plants using solid or liquid fuels with the exception of gas turbines and gas engines
Total rated thermal input (MW)
Coal and lignite and other solid fuels
Biomass
Peat
Liquid fuels
50-100
400
200
300
350
100-300
200
200
300
250 in case of fluidised bed combustion
200
> 300
150
200 in case of circulating or pressurised fluidised bed combustion
150
150
200 in case of fluidised bed combustion
150

---