Division 2 Sampling frequencies

United Kingdom

Original text. Later amendments are not shown.

Table 1. Minimum frequency of sampling and analysis for compliance monitoring
Note 1: A supply zone is a geographically defined area within which water intended for human consumption comes from one or more sources and within which the water quality can be considered as being approximately uniform.
Note 2: The volumes are calculated as averages taken over a calendar year. The number of inhabitants in a supply zone may be used instead of the volume of water to determine the minimum frequency, assuming water consumption of 200 l/(day*capita).
Note 3: The frequency indicated is calculated as follows: e.g. 4 300 m3/d = 16 samples for Group A parameters (four for the first 1 000 m3/d + 12 for additional 3 300 m3/d).
Note 4: For water suppliers, where an exemption has not been granted under point (b) of Article 3(3), Member States shall lay down the minimum sampling frequency for parameters of Groups A and B, provided that core parameters are monitored at least once per year.
Note 5: Member States may reduce the sampling frequency, provided that all parameters set in accordance with Article 5 are monitored at least once every six years and are monitored in cases where a new water source is integrated into the water supply system or changes to that system, as a result of which a potentially adverse effect on the quality of water is to be expected, are made.
Volume of water distributed or produced each day within a supply zone(See Notes 1 and 2) m3 Group A parameternumber of samples per yearGroup B parameternumber of samples per year
< 10> 0 (See Note 4)> 0 (See Note 4)
≥ 10≤ 10021 (See Note 5)
> 100≤ 1 00041
> 1 000≤ 10 000

4 for the first 1 000 m3/d

+ 3 for each additional 1 000 m3/d and part thereof of the total volume

(See Note 3)

1 for the first 1 000 m3/d

+ 1 for each additional 4 500 m3/d and part thereof of the total volume

(See Note 3)

> 10 000≤ 100 000

3 for first 10 000 m3/d

+ 1 for each additional 10 000 m3/d and part thereof of the total volume

(See Note 3)

> 100 000

12 for first 100 000 m3/d

+ 1 for each additional 25 000 m3/d and part thereof of the total volume

(See Note 3)