OpenLegislation

Division 1 Chemical and indicator parameters

United Kingdom

Original text. Later amendments are not shown.

For the parameters set out in Table 1 of this Annex, the method of analysis used shall, as a minimum, be capable of measuring concentrations equal to the parametric value with a limit of quantification, as defined in point (2) of Article 2 of Commission Directive 2009/90/ECf1, of 30 % or less of the relevant parametric value and an uncertainty of measurement as specified in Table 1 of this Annex. The result shall be expressed using at least the same number of significant figures as for the parametric value referred to in Parts B and C of Annex I to this Directive.

The uncertainty of measurement laid down in Table 1 shall not be used as an additional tolerance to the parametric values set out in Annex I.

Table 1. Minimum performance characteristic ‘Uncertainty of measurement’

ParametersUncertainty of measurement(See Note 1)% of the parametric value (except for pH)Notes
Aluminium25
Ammonium40
Acrylamide30
Antimony40
Arsenic30
Benzo(a)pyrene50See Note 2
Benzene40
Bisphenol A50
Boron25
Bromate40
Cadmium25
Chloride15
Chlorate40
Chlorite40
Chromium30
Copper25
Cyanide30See Note 3
1,2-dichloroethane40
Epichlorohydrin30
Fluoride20
HAAs50
Hydrogen ion concentration pH0,2See Note 4
Iron30
Lead30
Manganese30
Mercury30
Microcystin-LR30
Nickel25
Nitrate15
Nitrite20
Oxidisability50See Note 5
Pesticides30See Note 6
PFAS50
Polycyclic aromatic hydrocarbons40See Note 7
Selenium40
Sodium15
Sulphate15
Tetrachloroethene40See Note 8
Trichloroethene40See Note 8
Trihalomethanes – total40See Note 7
Total organic carbon (TOC)30See Note 9
Turbidity30See Note 10
Uranium30
Vinyl chloride50

Annotations

Footnotes

f1