Article 7 Indirect measuring methods
United Kingdom
To identify a leakage, certified personnel shall carry out a visual and manual check of the equipment and analyse one or more of the following parameters:
pressure;
temperature;
compressor current;
liquid levels;
recharge volume.
Any presumption of fluorinated greenhouse gas leakage shall be followed by an examination for leakage using a direct method as specified in Article 6.
One or more of the following situations shall constitute a presumption of leakage:
a fixed leakage detection system indicates leakage;
the equipment produces abnormal noises or vibration or ice formation or insufficient cooling capacity;
indications of corrosion, oil leaks and component or material damage at possible leakage points;
indications of leakage from sight glasses or level indicators or other visual aids;
indications of damage in safety switches, pressure switches, gauges and sensor connections;
deviations from normal operational conditions indicated by the parameters analysed, including readings from real time electronic systems;
other signs indicating refrigerant charge loss.