Division 2.6.4.2 In the case of mixtures containing known flammable liquids in defined concentrations, although they may contain non-volatile components e.g. polymers, additives, the flash point need not be determined experimentally if the calculated flash point of the mixture, using the method given in 2.6.4.3 below, is at least 5 °C greater than the relevant classification criterion and provided that:F1
United Kingdom
- (a)
the composition of the mixture is accurately known (if the material has a specified range of composition, the composition with the lowest calculated flash point shall be selected for assessment);
- (b)
the lower explosion limit of each component is known (an appropriate correlation has to be applied when these data are extrapolated to other temperatures than test conditions) as well as a method for calculating the lower explosion limit F2of the mixture;
- (c)
the temperature dependence of the saturated vapour pressure and of the activity coefficient is known for each component as present in the mixture;
- (d)
the liquid phase is homogeneous.
Annotations
Textual amendments
- F1
- F2
Footnotes
- f1
-
Up to now, the calculation method is validated for mixtures containing up to six volatile components. These components may be flammable liquids like hydrocarbons, ethers, alcohols, esters (except acrylates), and water. It is however not yet validated for mixtures containing halogenated, sulphurous, and/or phosphoric compounds as well as reactive acrylates.
- f2
-
If the calculated flash point is less than 5 °C greater than the relevant classification criterion, the calculation method may not be used and the flash point shall be determined experimentally.