OpenLegislation

Division 2 Fan energy efficiency requirements

United Kingdom

Original text. Later amendments are not shown.

The minimum energy efficiency requirements for fans are set out in Tables 1 and 2.

Table 1

First tier minimum energy efficiency requirements for fans from 1 January 2013

Fan typesMeasurement category(A-D)Efficiency category(static or total)Power range P in kWTarget energy efficiencyEfficiency grade(N)
Axial fanA, Cstatic0,125 ≤ P ≤ 10ηtarget = 2,74 · ln(P) – 6,33 + N36
10 < P ≤ 500ηtarget = 0,78 · ln(P) – 1,88 + N
B, Dtotal0,125 ≤ P ≤ 10ηtarget = 2,74 · ln(P) – 6,33 + N50
10 < P ≤ 500ηtarget = 0,78 · ln(P) – 1,88 + N
Centrifugal forward curved fan and centrifugal radial bladed fanA, Cstatic0,125 ≤ P ≤ 10ηtarget = 2,74 · ln(P) – 6,33 + N37
10 < P ≤ 500ηtarget = 0,78 · ln(P) – 1,88 + N
B, Dtotal0,125 ≤ P ≤ 10ηtarget = 2,74 · ln(P) – 6,33 + N42
10 < P ≤ 500ηtarget = 0,78 · ln(P) – 1,88 + N
Centrifugal backward curved fan without housingA, Cstatic0,125 ≤ P ≤ 10ηtarget = 4,56 · ln(P) – 10,5 + N58
10 < P ≤ 500ηtarget = 1,1 · ln(P) – 2,6 + N
Centrifugal backward curved fan with housingA, Cstatic0,125 ≤ P ≤ 10ηtarget = 4,56 · ln(P) – 10,5 + N58
10 < P ≤ 500ηtarget = 1,1 · ln(P) – 2,6 + N
B, Dtotal0,125 ≤ P ≤ 10ηtarget = 4,56 · ln(P) – 10,5 + N61
10 < P ≤ 500ηtarget = 1,1 · ln(P) – 2,6 + N
Mixed flow fanA, Cstatic0,125 ≤ P ≤ 10ηtarget = 4,56 · ln(P) – 10,5 + N47
10 < P ≤ 500ηtarget = 1,1 · ln(P) – 2,6 + N
B, Dtotal0,125 ≤ P ≤ 10ηtarget = 4,56 · ln(P) – 10,5 + N58
10 < P ≤ 500ηtarget = 1,1 · ln(P) – 2,6 + N
Cross flow fanB, Dtotal0,125 ≤ P ≤ 10ηtarget = 1,14 · ln(P) – 2,6 + N13
10 < P ≤ 500ηtarget = N

Table 2

Second tier minimum energy efficiency requirements for fans from 1 January 2015

Fan typesMeasurement category(A-D)Efficiency category(static or total)Power range P in kWTarget energy efficiencyEfficiency grade(N)
Axial fanA, Cstatic0,125 ≤ P ≤ 10ηtarget = 2,74 · ln(P) – 6,33 + N40
10 < P ≤ 500ηtarget = 0,78 · ln(P) – 1,88 + N
B, Dtotal0,125 ≤ P ≤ 10ηtarget = 2,74 · ln(P) – 6,33 + N58
10 < P ≤ 500ηtarget = 0,78 · ln(P) – 1,88 + N
Centrifugal forward curved fan and centrifugal radial bladed fanA, Cstatic0,125 ≤ P ≤ 10ηtarget = 2,74 · ln(P) – 6,33 + N44
10 < P ≤ 500ηtarget = 0,78 · ln(P) – 1,88 + N
B, Dtotal0,125 ≤ P ≤ 10ηtarget = 2,74 · ln(P) – 6,33 + N49
10 < P ≤ 500ηtarget = 0,78 · ln(P) – 1,88 + N
Centrifugal backward curved fan without housingA, Cstatic0,125 ≤ P ≤ 10ηtarget = 4,56 · ln(P) – 10,5 + N62
10 < P ≤ 500ηtarget = 1,1 · ln(P) – 2,6 + N
Centrifugal backward curved fan with housingA, Cstatic0,125 ≤ P ≤ 10ηtarget = 4,56 · ln(P) – 10,5 + N61
10 < P ≤ 500ηtarget = 1,1 · ln(P) – 2,6 + N
B, Dtotal0,125 ≤ P ≤ 10ηtarget = 4,56 · ln(P) – 10,5 + N64
10 < P ≤ 500ηtarget = 1,1 · ln(P) – 2,6 + N
Mixed flow fanA, Cstatic0,125 ≤ P ≤ 10ηtarget = 4,56 · ln(P) – 10,5 + N50
10 < P ≤ 500ηtarget = 1,1 · ln(P) – 2,6 + N
B, Dtotal0,125 ≤ P ≤ 10ηtarget = 4,56 · ln(P) – 10,5 + N62
10 < P ≤ 500ηtarget = 1,1 · ln(P) – 2,6 + N
Cross flow fanB, Dtotal0,125 ≤ P ≤ 10ηtarget = 1,14 · ln(P) – 2,6 + N21
10 < P ≤ 500ηtarget = N