Division 2 Fan energy efficiency requirements
United Kingdom
The minimum energy efficiency requirements for fans are set out in Tables 1 and 2.
Table 1
First tier minimum energy efficiency requirements for fans from 1 January 2013
| Fan types | Measurement category(A-D) | Efficiency category(static or total) | Power range P in kW | Target energy efficiency | Efficiency grade(N) |
|---|---|---|---|---|---|
| Axial fan | A, C | static | 0,125 ≤ P ≤ 10 | ηtarget = 2,74 · ln(P) – 6,33 + N | 36 |
| 10 < P ≤ 500 | ηtarget = 0,78 · ln(P) – 1,88 + N | ||||
| B, D | total | 0,125 ≤ P ≤ 10 | ηtarget = 2,74 · ln(P) – 6,33 + N | 50 | |
| 10 < P ≤ 500 | ηtarget = 0,78 · ln(P) – 1,88 + N | ||||
| Centrifugal forward curved fan and centrifugal radial bladed fan | A, C | static | 0,125 ≤ P ≤ 10 | ηtarget = 2,74 · ln(P) – 6,33 + N | 37 |
| 10 < P ≤ 500 | ηtarget = 0,78 · ln(P) – 1,88 + N | ||||
| B, D | total | 0,125 ≤ P ≤ 10 | ηtarget = 2,74 · ln(P) – 6,33 + N | 42 | |
| 10 < P ≤ 500 | ηtarget = 0,78 · ln(P) – 1,88 + N | ||||
| Centrifugal backward curved fan without housing | A, C | static | 0,125 ≤ P ≤ 10 | ηtarget = 4,56 · ln(P) – 10,5 + N | 58 |
| 10 < P ≤ 500 | ηtarget = 1,1 · ln(P) – 2,6 + N | ||||
| Centrifugal backward curved fan with housing | A, C | static | 0,125 ≤ P ≤ 10 | ηtarget = 4,56 · ln(P) – 10,5 + N | 58 |
| 10 < P ≤ 500 | ηtarget = 1,1 · ln(P) – 2,6 + N | ||||
| B, D | total | 0,125 ≤ P ≤ 10 | ηtarget = 4,56 · ln(P) – 10,5 + N | 61 | |
| 10 < P ≤ 500 | ηtarget = 1,1 · ln(P) – 2,6 + N | ||||
| Mixed flow fan | A, C | static | 0,125 ≤ P ≤ 10 | ηtarget = 4,56 · ln(P) – 10,5 + N | 47 |
| 10 < P ≤ 500 | ηtarget = 1,1 · ln(P) – 2,6 + N | ||||
| B, D | total | 0,125 ≤ P ≤ 10 | ηtarget = 4,56 · ln(P) – 10,5 + N | 58 | |
| 10 < P ≤ 500 | ηtarget = 1,1 · ln(P) – 2,6 + N | ||||
| Cross flow fan | B, D | total | 0,125 ≤ P ≤ 10 | ηtarget = 1,14 · ln(P) – 2,6 + N | 13 |
| 10 < P ≤ 500 | ηtarget = N |
Table 2
Second tier minimum energy efficiency requirements for fans from 1 January 2015
| Fan types | Measurement category(A-D) | Efficiency category(static or total) | Power range P in kW | Target energy efficiency | Efficiency grade(N) |
|---|---|---|---|---|---|
| Axial fan | A, C | static | 0,125 ≤ P ≤ 10 | ηtarget = 2,74 · ln(P) – 6,33 + N | 40 |
| 10 < P ≤ 500 | ηtarget = 0,78 · ln(P) – 1,88 + N | ||||
| B, D | total | 0,125 ≤ P ≤ 10 | ηtarget = 2,74 · ln(P) – 6,33 + N | 58 | |
| 10 < P ≤ 500 | ηtarget = 0,78 · ln(P) – 1,88 + N | ||||
| Centrifugal forward curved fan and centrifugal radial bladed fan | A, C | static | 0,125 ≤ P ≤ 10 | ηtarget = 2,74 · ln(P) – 6,33 + N | 44 |
| 10 < P ≤ 500 | ηtarget = 0,78 · ln(P) – 1,88 + N | ||||
| B, D | total | 0,125 ≤ P ≤ 10 | ηtarget = 2,74 · ln(P) – 6,33 + N | 49 | |
| 10 < P ≤ 500 | ηtarget = 0,78 · ln(P) – 1,88 + N | ||||
| Centrifugal backward curved fan without housing | A, C | static | 0,125 ≤ P ≤ 10 | ηtarget = 4,56 · ln(P) – 10,5 + N | 62 |
| 10 < P ≤ 500 | ηtarget = 1,1 · ln(P) – 2,6 + N | ||||
| Centrifugal backward curved fan with housing | A, C | static | 0,125 ≤ P ≤ 10 | ηtarget = 4,56 · ln(P) – 10,5 + N | 61 |
| 10 < P ≤ 500 | ηtarget = 1,1 · ln(P) – 2,6 + N | ||||
| B, D | total | 0,125 ≤ P ≤ 10 | ηtarget = 4,56 · ln(P) – 10,5 + N | 64 | |
| 10 < P ≤ 500 | ηtarget = 1,1 · ln(P) – 2,6 + N | ||||
| Mixed flow fan | A, C | static | 0,125 ≤ P ≤ 10 | ηtarget = 4,56 · ln(P) – 10,5 + N | 50 |
| 10 < P ≤ 500 | ηtarget = 1,1 · ln(P) – 2,6 + N | ||||
| B, D | total | 0,125 ≤ P ≤ 10 | ηtarget = 4,56 · ln(P) – 10,5 + N | 62 | |
| 10 < P ≤ 500 | ηtarget = 1,1 · ln(P) – 2,6 + N | ||||
| Cross flow fan | B, D | total | 0,125 ≤ P ≤ 10 | ηtarget = 1,14 · ln(P) – 2,6 + N | 21 |
| 10 < P ≤ 500 | ηtarget = N |